UPS YUNTO P Series (250/500/750/1250)
From HwB
Pinout
9 PIN D-SUB FEMALE at the UPS.
Pin | Name | Dir | Description |
---|---|---|---|
1 | Battery Mode | out | This pin is shorted to PIN 5 (ground) if the mains power supply fails or is out of tolerance. (NORMALLY OPEN) |
2 | - | - | - |
3 | - | - | - |
4 | - | - | - |
5 | Ground | - | Ground terminal and common root of contacts at PIN 1, 8 and 9 |
6 | - | - | - |
7 | UPS shut-down | IN | If a positive signal level (+5V to +12V DC) is applied, the UPS system switches off (PIN 5 is ground) |
8 | Battery Capacity Low | OUT | This pin is shorted to PIN 5 (ground) if the batteries have been discharged to such an extent that the remaining stored energy time is less than 2 minutes. (NORMALLY OPEN) |
9 | Battery Mode | OUT | The connection between this pin and PIN 5 (ground) is disconnected if the main power supply fails oe is out of tolerance. (NORMALLY CLOSED) |
Note: Direction is relative to UPS.